16
Icon Displayed text* Description Name
General Parameters General parameters GENUNIT
Temperature Temperatures TEMP
Pressure Pressures PRESSURE
Inputs Inputs status INPUTS
Outputs Outputs status OUTPUTS
Pump Status Pump status PUMPSTAT
Runtime Run times RUNTIME
DC Free Cooling
Status
Dry Cooler - Free
Cooling
FCOOL_ST
Modes Modes status MODES
Setpoint Setpoints SETPOINT
Conguration Conguration menu CONFIG
*Depends on the selected language (English by default).
CAUTION
Since specic units may not include additional features,
some tables may contain parameters that cannot be
congured for a given unit.
7 - PARAMETERS
7.1 - Main menu
General Parameters Menu – GENUNIT
Point name Status Unit Displayed text* Description
1 CTRL_TYP 0 to 2 - Local=0 Net.=1 Remote=2 Operating mode: 0 = Local, 1 = Network,
2 = Remote
2 STAT US xxx - Running Status Unit running status: 0 = O, 1 = Running, 2 = Stopping,
3 = Delay, 4 = Trip out, 5 = Ready, 6 = Override, 7 =
Defrost, 8 = Run Test, 9 = Test
3 ALM xxx - Alarm State Alarm status
4 min_left 0 to 0 min Minutes Left for Start Minutes left before the unit start-up
5 HEATCOOL Heat/Cool status Heating/Cooling status
6 HC_SEL 0 to 2 - Heat/Cool Select Heating/Cooling selection
0=Cool 1=Heat 2=Auto 0 = Cool, 1 = Heat, 2 = Auto
7 SP_SEL 0 to 2 - Setpoint Select Setpoint select
0=Auto. 1=Spt1. 2=Spt2 0 = Auto, 1 = Setpoint 1, 2 = Setpoint 2
8 SP_OCC no/yes - Setpoint Occupied? Setpoint occupied?
9 CHIL_S_S dsable/enable - Net.: Cmd Start/Stop Unit start/stop via Network: When the unit is in Network
mode, start/stop command can be forced
10 CHIL_OCC no/yes - Net.: Cmd Occupied Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
11 CAP_T 0 to 100 % Percent Total Capacity Total unit capacity
12 CAPA_T 0 to 100 % Circuit A Total Capacity Total capacity, circuit A
13 CAPB_T 0 to 100 % Circuit B Total Capacity Total capacity, circuit B
14 DEM_LIM 0 to 100 %
Active Demand Limit Val
Active demand limit value: When the unit is Network
mode, the minimum value will be used compared to
the status of the external limit switch contact and the
demand limit switch setpoint
15 SP - °C / °F Current Setpoint Current setpoint
16 CTRL_PNT -20.0 to 67.0
-4.0 to 153.0
°C
°F
Control Point
Control point: Water temperature that the unit must
produce
17 EMSTOP dsable/enable - Emergency Stop Emergency stop
*Depends on the selected language (English by default).