Temperature Menu – TEMP
Point name
Status Unit Displayed text* Description
1 EWT - °C / °F Entering Water Temp Entering water temperature: Used for capacity control
2 LWT - °C / °F Leaving Water Temp Leaving water temperature: Used for capacity control
3 OAT - °C / °F External Temperature Outdoor air temperature: Used to determine a number of control
mechanisms such as heat/cool changeover, water exchanger
heater operation, defrost cycle
4 CHWSTEMP - °C / °F Common Master/Slave Temp Common master/slave temperature
5 SCT_A - °C / °F Saturated Cond Tmp A Saturated condensing temperature, circuit A
6 SST_A - °C / °F Saturated Suction Tmp A Saturated suction temperature, circuit A
7 SCT_B - °C / °F Saturated Cond Tmp B Saturated condensing temperature, circuit B
8 SST_B - °C / °F Saturated Suction Tmp B Saturated suction temperature, circuit B
9 DEFRT_A - °C / °F Defrost Temp Cir A Defrost temperature, circuit A (heat pumps only)
10 DEFRT_2 - °C / °F Defrost Temp Second Coil Defrost temperature on the second coil on circuit A (heat pumps
only)
11 sgtc1 - °C / °F Suction Gas Temp Coil 1 Suction gas temperature coil 1
12 sgtc2 - °C / °F Suction Gas Temp Coil 2 Suction gas temperature coil 2
*Depends on the selected language (English by default).
Pressure Menu – PRESSURE
Point name Status
Unit Displayed text* Description
1 DP_A - kPa / PSI Discharge Pressure A Compressor discharge pressure, circuit A
2 SP_A - kPa / PSI Suction Pressure A Compressor suction pressure, circuit A
3 DP_B - kPa / PSI Discharge Pressure B Compressor discharge pressure, circuit B
4 SP_B - kPa / PSI Suction Pressure B Compressor suction pressure, circuit B
*Depends on the selected language (English by default).
Inputs Menu – INPUTS
Point name Status
Unit Displayed text* Description
1 ONOFF_SW open/close - Remote On/O Switch Remote On/O switch
2 HC_SW open/close - Remote Heat/Cool Switch Remote Heat/Cool switch
3 on_ctrl xxx - Current Control Current control status: O, On Cool, On Heat, On Auto
4 SETP_SW open/close - Remote Setpoint Switch Remote setpoint switch
5 LIM_SW1 open/close - Limit Switch 1 Demand limit switch 1
6 LIM_SW2 open/close - Limit Switch 2 Demand limit switch 2
7 LIM_ANAL - mA Limit Analog Input Limit Analog Input 4-20mA
8 FLOW_SW open/close - Flow Switch Water exchanger ow switch
9 leak_v - V Leakage detector #1 val Leakage detector 1
10 leak_2_v - V Leakage detector #2 val Leakage detector 2
11 DSHT_SW open/close - Desuperheater Switch Desuperheater switch
12 PWRIN_ST open/close - Power Input Stable Power input stable
13 HP_SWA open/close - HP Switch Circuit A High pressure switch, circuit A
14 HP_SWA3B open/close - HP Switch Circuit A3/B High pressure switch, circuit B
15 bacdongl no/yes - BACnet Dongle BACnet dongle status (BACnet option)
*Depends on the selected language (English by default).