Outputs Menu – OUTPUTS
Point name Status Unit Displayed text* Description
1 CP_A1 o/on - Compressor A1 Output Compressor A1 status
2 CP_A2 o/on - Compressor A2 Output Compressor A2 status
3 CP_A3 o/on - Compressor A3 Output Compressor A3 status
4 FAN_A1LS o/on - Fan A1LS Output Fan A1 low speed status
5 FAN_A1HS o/on - Fan A1HS Output Fan A1 high speed status
6 FAN_A2LS o/on - Fan A2LS Output Fan A2 low speed status
7 FAN_A2HS o/on - Fan A2HS Output Fan A2 high speed status
8 HD_POS_A - % Head Pressure Position A Head pressure, circuit A
9 EXVPosA - % EXV Position Circuit A EXV position, circuit A
10 EXVNPosA - % EXV Next Pos Circuit A EXV next position, circuit A
11 RV_A o/on - 4 Way Refrigerant ValveA 4-way refrigerant valve, circuit A: Used to manage cooling / heating
/ defrost operation (heat pumps)
12 CP_B1 o/on - Compressor B1 Output Compressor B1 status
13 CP_B2 o/on - Compressor B2 Output Compressor B2 status
14 FAN_B1LS o/on - Fan B1LS Output Fan B1 low speed status
15 FAN_B1HS o/on - Fan B1HS Output Fan B1 high speed status
16 HD_POS_B - % Head Pressure Position B Head pressure, circuit B
17 EXVPosB - % EXV Position Circuit B EXV position, circuit B
18 EXVNPosB - % EXV Next Pos Circuit B EXV next position, circuit B
19 RV_B o/on - 4 Way Refrigerant ValveB 4-way refrigerant valve, circuit B: Used to manage cooling/heating/
defrost operation (heat pumps)
20 C_HEATER o/on - Cooler & Drain Pan Heatr Water exchanger / Drain pan heater
21 BOILER o/on - Boiler Command Boiler status
22
EHS_STEP - - Electrical Heat Stage Electric heating stages
23 ALARM_R o/on - Alarm Relay Status Alarm relay status
24 RUN_R o/on - Running Status Unit ON relay
25 OIL_VALV o/on - Oil Valve Status Oil valve status
*Depends on the selected language (English by default).
Pump Status Menu – PUMPSTAT
Point name Status Unit Displayed text* Description
1 CPUMP_1 o/on - Water Pump #1 Command Water pump 1 command
2 CPUMP_2 o/on - Water Pump #2 Command Water pump 2 command
3 ROT_PUMP no/yes - Rotate Pumps Now? Water exchanger pumps rotation
4 W_P_IN - kPa / PSI Inlet Water Pressure Inlet water pressure
5 W_P_OUT - kPa / PSI Outlet Water Pressure Outlet water pressure
6 WP_CALIB no/yes - Water Pressure Calibrat Water pressure calibration
7 WP_OFFST - kPa / PSI Water Pressure Oset Water pressure oset
8 DP_FILTR - kPa / PSI Delta Water Press. Filt Delta water pressure ltration
9 WP_MIN - kPa / PSI Mini Water Pressure Minimum water pressure
10 WAT_FLOW - l/s / GPS Water Flow Water ow status
11 CAPPOWER - kW Actual Power Capacity Actual power capacity
12 p_dt_spt - ^C / ^F Water DT Setpoint Water discharge temperature setpoint
13 p_dp_spt - kPa / PSI Water DP Setpoint Water discharge pressure setpoint
14 drvp_pct - % Pump Drive Percent Pump drive percent
15 drvp_pwr - kW Pump Drive Power Pump drive power
16 drvp_i - A Pump Drive Amps Pump drive (A)
17 drvp_ver xxx - Pump Drive Version Pump drive version
*Depends on the selected language (English by default).