62-61753-21   
22  LOW SUCTION SUPERHEAT 
  TRIGGER ON: 
  "Check Suction Temperature Sensor" and/or "Check Evaporator Temperature Sensor" alarms are not 
active (refer to alarm 127 and/or 131 first) and: 
  Compressor suction superheat (Compressor Suction Temperature (CST) minus saturated temperature 
for Compressor Suction Pressure (CSP) is less than 5°C (9°F) for more than 2 minutes. 
  UNIT CONTROL:   Engine operation: Shutdown and alarm. 
      Standby operation: refrigeration system shutdown and alarm with PSCON  
      still energized. 
  RESET CONDITION: Auto reset after 15 minutes, or alarm may be manually reset via keypad or by 
turning the unit off, then back on again.  
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active 
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if 
any active alarm occurs. Continue with the steps below as necessary. 
a. Install Manifold Test Set and check 
and compare compressor dis-
charge, suction and evaporator 
outlet pressure with those shown 
on the microprocessor display. 
Pressures must have the same reading on gauges & 
on microprocessor display. 
NOTE: Microprocessor suction (CSP) and evaporator 
(EVOP) pressure readings have a maximum value of 
7.5 bar (100 psig) The actual suction pressure must be 
lower than 100 psig in order to perform this test. 
a. Check evaporator section, return 
air bulkhead, air chute, cleanliness 
of evap. coil and airflow. 
a. Clear Active Alarm list, then run 
Pretrip & check for any new 
alarms. 
Any active alarms must be corrected and cleared be-
fore proceeding. 
a. Check operation of EVXV