62-61753-21   
4  The battery is fully charged - Amperage. 
The microprocessor will calculate the average  current 
draw  over  a  20  second  period.  Once  this  average 
drops  below  the  selected  value,  shutdown  will  be  al-
lowed. The CURRENT FOR START/STOP SHUTOFF 
is  selected  in  the  microprocessor  Configurations.  The 
value may be set from 1 to 10 amps in 0.5 amp inter-
vals. The factory default setting is 5 amps. 
5  The refrigerated compartment temperature is at 
setpoint. 
Shutdown will be allowed  when  the active probe tem-
perature  is  within  ±0.3°C  (±0.5°F)  of  set  point,  in  the 
Perishable Range. In the Frozen Range, shutdown will 
be allowed when the active probe temperature is with-
in  ±0.3°C  -  the  FROZEN  SHUT  DOWN  OFFSET 
(±0.5°F-  the  FROZEN  SHUT  DOWN  OFFSET)  of  set 
point. 
The  FROZEN  SHUT  DOWN  OFFSET  Functional  Pa-
rameter  may  be  set  from  0°C  (0°F)  to  2°C  (3.6°F)  in 
0.5°(C  or  F)  increments.  The  factory default setting is 
0°C (32°F). 
4.3.3  Re-Start Parameters 
While the unit is in Start-Stop Off, restart will be initiat-
ed when one of the following conditions occurs: 
1  Engine coolant temperature drops below se-
lected microprocessor Configuration value. 
If in Engine Operation, the microprocessor will monitor 
coolant  temperature.  If  coolant  temperature  drops 
below  the  ENGINE  TEMPERATURE  FOR  RESTART 
Configuration  value  the  engine  will  be  started.  The 
Configuration value may be set from -12.2°C (10°F) to 
0°C  (32°F)  in  0.5°(C  or  F)  increments.  The  factory 
default setting is 0°C (32°F). 
2  Battery voltage falls below selected micropro-
cessor Configuration value. 
The  microprocessor  will  monitor  battery  voltage.  If 
battery  voltage  is  at  or  below  the  VOLTAGE  FOR 
START/STOP  RESTART  Configuration  value  the  en-
gine will be started. The value may be set from 12.0 to 
12.8 volts. The factory default setting is 12.2 volts. 
TIP 
While the unit is running, the status of the unit 
battery can be readily checked by reading the 
Battery  Voltage  in  the  Data  List.  If  "OK."  ap-
pears after the voltage reading, battery voltage 
is sufficient to allow the unit to cycle off. 
3  Refrigerated compartment Temperature has 
exceeded the microprocessor Functional Pa-
rameter value. 
The  microprocessor  continually  monitors  the  refriger-
ated  compartment  temperature.  If  the  temperature 
should  drift  outside  the  OVERRIDE  TEMPERATURE 
Functional  Parameter  value  the  unit  will  be  restarted. 
The value may be set from 2°C (3.6°F) to 10°C (18°F) 
in  0.5°  increments.  The  factory  default  setting  is  6°C 
(11°F). 
4  The Maximum Off Time has expired. 
In some ambient conditions, there are times when the 
unit may be off for very long periods of time. To ensure 
that  the  entire  load  stays  within  required  temperature 
ranges, the MAXIMUM OFF TIME Functional Parame-
ter  may  be  used  to  force  the  unit  to  restart.  The  pa-
rameter  value  may  be  set  to  OFF  or  from  10  to 
225 minutes  in  1  minute  intervals.  The  factory  default 
setting is OFF. 
5  The minimum off time has expired 
The  MINIMUM  OFF  TIME  Functional  Parameter  set-
ting allows the unit to remain off for extended periods 
of time, maximizing fuel/power economy. The unit may 
not  be  restarted  until  the  MINIMUM  OFF  TIME  has 
expired  and  one  of  the  other  Re-Start  parameters  is 
calling  for  re-start.  The  parameter  value  may  be  set 
from 10 to 90 minutes in 1 minute intervals. The facto-
ry default setting is 20 minutes. 
4.4  CONTINUOUS OPERATION  
In  Continuous  Operation,  the  unit  will  not  shut  down 
except in response to a shut down alarm. Continuous 
Operation is normally used for fresh produce and other 
sensitive  product  loads.  The  Start-Stop/Continuous 
key  is  pressed  to  switch  between  Continuous  and 
Start-Stop  operating  modes.  The  corresponding  LED 
will be illuminated. 
NOTE  
The microprocessor may be locked so that the 
unit  will  always  operate  in  Start-Stop  or  in 
Continuous  whenever  the  setpoint  is  within  a 
specific  range.  Refer  to  Range  Lock  (Section 
4.6.2)  and  ProductShield  (Section  4.6.3)  for 
additional information. 
4.5  TEMPERATURE CONTROL 
4.5.1  Temperature Determination 
The  microprocessor  monitors  the  temperature  read-
ings  from  the  supply  and  return  temperature  sensors 
to determine the  mode  of  operation  required  to  main-
tain  refrigerated  compartment  temperature  in  accord-
ance with the Setpoint. 
Based on the sensor readings and time, the micropro-
cessor  will calculate  a Controlling  Temperature  value. 
This value is calculated to provide smoother tempera-
ture control and transition between the modes of oper-
ation. The modes of operation include Pulldown, Cool, 
Heat and Null. 
4.5.2  Heat/Cool/Null Mode Switching Logic 
Operation in Cool, Heat and Null modes is determined 
in accordance with the calculated Controlling Temper-
ature value (CT) and the difference between this value 
and Setpoint (SP) in accordance with the following: