62-61753-21     
4. Engine Coolant Warm-Up  
The  engine  will  run  in  low  speed  until  the  coolant  is 
above 50°C (122°F).  
5. Door/Remote Switch Configuration 
If the Door/Remote Switch Configuration is set for low 
speed,  the  engine  will  run  in  low  speed  when  the 
door/remote switch is open/active. 
6. Auto Silent Mode 
If the engine is restarted from a Start/Stop off cycle for 
any  reason  except  a  Start/Stop  Parameter  Override 
Temperature the engine will operate in low speed until 
the overriding condition is met 
7. Low Speed To High Speed Delay 
  The compressor must operate for 2 minutes before 
transition to high speed is allowed. 
  The  time  value  entered  in  the  High  Speed  Delay 
Configuration  must  be  expired  before  transition  to 
high speed is allowed. 
  The  time  value  entered  in  the  Low  Speed  Startup 
Minutes  Functional  Parameter  (for  Start/Stop  or 
Continuous)  must  be  expired  before  transition  to 
high speed is allowed. 
8. Operation With A Frozen Setpoint 
  If  in  Start/Stop  mode  with  a  setpoint  in  the  frozen 
range (-12°C [+10.4°F] or below), and the minimum 
run  time  has  expired,  and  the  refrigerated  com-
partment temperature is not at setpoint, the engine 
will transition to high speed. 
  If setpoint is in the frozen range, and the refrigerat-
ed compartment temperature is below setpoint, the 
engine will transition to low speed. 
9. Low Suction Pressure 
The  microprocessor  monitors  the  signal  provided  by 
the  Suction  Pressure  Transducer.  If  the  suction  pres-
sure  falls  below  -0.14  bar  (-2psig)  for  more  than  20 
seconds,  the  engine  will  operate  in  low  speed  for  a 
minimum of 5 minutes, then remain in low speed until 
the suction pressure is greater than -0.14 bar (-2psig). 
10. Operation With A Perishable Setpoint 
  If in Start/Stop Operation with a setpoint in the per-
ishable range (above -12°C [+10.4°F]) and all con-
ditions for an OFF Cycle have been met except for 
setpoint,  the  engine  will  operate  in  high  speed  to 
pull down to setpoint and cycle off quicker. 
NOTE 
Generally, the unit will go into an off cycle from 
high  speed  when  this  condition  occurs.  How-
ever, if one of the required conditions for shut 
down  is  no  longer  met  during  this  time,  (for 
example,  the  battery  voltage  drops  below  the 
configured  value,  or  the  charging  amps  in-
crease above the configured value, or the en-
gine  coolant  temperature  drops  below  122°F 
(50°C),  the  engine  may  return  to  low  speed 
operation until the shut down condition is satis-
fied, then shut down from low speed. 
  If  in  Continuous  Operation  with  a  setpoint  in  the 
perishable  range  (above  -12°C  [+10.4°F])  and  the 
High  Speed  Pulldown  Configuration  is  set  to  YES, 
the  engine  will  operate  in  high  speed  until  the  re-
frigerated  compartment  temperature  is  within 
±0.2°C (0.4°F) of setpoint. 
11. Product Shield 
  If the ProductShield High Air Configuration is set to 
ON, the engine will operate in high speed whenev-
er  the  ambient  air  temperature  is  outside  the  tem-
perature range selected. 
  If the ProductShield Delta-T Configuration is set to 
ON, the engine will operate in high speed whenev-
er  the  Delta-T  is  greater  than  the  selected  value. 
(Refer  to  Section  4.6.3  for  more  information  on 
ProductShield.) 
4.7.4  Operating Mode Overrides 
With  the  complex  control  systems  in  use  with  the 
LogiCOLD  Microprocessor,  there  are  many  different 
reasons - other than the number of degrees the refrig-
erated compartment temperature is away from setpoint 
-  that  the  refrigeration  system  may  be  operating  in 
Economized Mode, Standard Mode or Bypass Mode.  
Operating Mode Overrides are: 
1. High Discharge Pressure 
If the microprocessor is requesting Economized Mode 
with  discharge  pressure  above  30.2  bar  (444.4  psig) 
or under a condition where the the compressor suction 
modulating valve (CSMV) has throttled more than 30% 
in an attempt to control rising discharge pressure, the 
system will be transitioned to Bypass Mode. 
2. High Generator Current 
If  the  system  is  operating  with  high  generator  current 
the microprocessor will throttle the compressor suction 
modulating valve (CSMV)  in an attempt to reduce the 
load.  If  additional  current  reduction  is  required  the 
microprocessor  will  transition  from  Economized  Mode 
to Standard Mode or Standard Mode to Bypass Mode 
as  required  to  prevent  the  engine  from  stalling.  As 
current  is  reduced,  the  microprocessor  will  reverse 
these  steps  to  provide  maximum  allowable  capacity. 
This action is called "staging". 
Downshift Staging: If the compressor suction modulat-
ing  valve  (CSMV)  has  throttled  more  than  30%  of  its 
available position due to high current and the absolute 
value  of  the  compressor  suction  modulating  valve 
(CSMV) position is less than 20%, operation will transi-
tion  from  Economized  to  Standard  Mode  or  from 
Standard to Bypass Mode. 
Upshift  Staging:  Bypass  to  Standard  Mode:  The  up-
shift will occur when the generator current is less than 
the allowed maximum generator current - (1 amp + an 
upshift  offset).  The  upshift  offset  is  0.5  amps  X  the 
number of failed upshift attempts. 
Upshift  Staging:  Standard  to  Economized  Mode:  The 
upshift  will  occur  when  the  generator  current  is  less 
than  the  allowed  maximum  generator  current  - 
(1.5 amp  +  an  upshift  offset).  The  upshift  offset  is 
0.5 amps X the number of failed upshift attemps.