62-61753-21   
23  A/C CURRENT OVER LIMIT (Continued) 
Check Generator Voltage (If Used When Alarm Occurred) 
a. Check voltage at GENCON L1-L2, 
L1-L3, L2-L3. 
Must be within voltage limits shown in Section 2.11. 
Check Power Source Voltage (If Used When Alarm Occurred) 
a. Check voltage at PSCON L1-L2, 
L1-L3, L2-L3. 
Must be within voltage limits shown in Section 2.11. 
Check Voltage Output From Contactors 
a. Check voltage at GENCON T1-T2, 
T1-T3, T2-T3. 
Must be within voltage limits shown in Section 2.11. 
b. Check voltage at CCON with com-
pressor operating. T1-T2, T1-T3, 
T2-T3. 
Must be within voltage limits shown in Section 2.11. 
Defective Overload Ground Fault Module (OGF) 
Check OGF. Refer to procedure for Alarm 100 
Verify AC Current Sensor Accuracy (CT2 & CT3) 
a. Place the SROS in the 
START / RUN position. 
Unit AC Current #1 and #2 reading in Data List must 
be 0.0 ± 1.0 amp.