62-61753-21
7-88
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
229 SERVICE SOON-PM #4 DUE
TRIGGER-ON: The Maintenance Hour Meter #4 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
a. Schedule unit into service facility
for maintenance
Must be done soon!
2
Perform Maintenance
a. Perform appropriate engine & unit
maintenance.
Follow maintenance interval recommendations in
Section 8.2.
3
Reset Maintenance Hour Meter #4
a. Reset hour meter for the next ser-
vice interval.
Reset Functional Parameter (refer to Table 3-2).
b. If hour meter interval is not set for
your requirements, reset the Con-
figuration, refer to Table 5-2.
Follow maintenance interval recommendations in
Section 8.2.
230 SERVICE SOON-PM #5 DUE
TRIGGER-ON: The Maintenance Hour Meter #5 time has expired.
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
a. Schedule unit into service facility
for maintenance.
Must be done soon!
2
Perform Maintenance
a. Perform appropriate engine & unit
maintenance.
Follow maintenance interval recommendations in
Section 8.2.
3
Reset Maintenance Hour Meter #5
a. Reset hour meter for the next ser-
vice interval.
Reset Functional Parameter (refer to Table 3-2).
b. If hour meter interval is not set for
your requirements, reset the Con-
figuration, refer to Table 5-2.
Follow maintenance interval recommendations in
Section 8.2.