62-61753-21     
245  CANNOT SAVE SETTING 
  TRIGGER-ON: There is an error in sending and saving new settings in the Microprocessor 
memory. 
  UNIT CONTROL: Alarm only. 
  RESET CONDITION: Alarm may be manually reset via Keypad or by turning the unit off, then back on 
again. 
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active 
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any 
active alarm occurs. Continue with the steps below as necessary. 
Check Microprocessor Software Revision 
a. Check Microprocessor Software 
Revision. 
Will be a 6 digit number. 
a. Place the SROS in the OFF posi-
tion for 30 seconds, then back to 
START / RUN. 
Will be a 6 digit number. 
Upgrade to the latest version. 
b. Check Active Alarm List. 
Alarm is cleared - microprocessor is OK. 
c. Alarm 245 can not be cleared. 
Unit will operate, but changes to the settings will not be 
retained in the microprocessor memory. Replace mi-
croprocessor. Refer to Section 5.4 
246  EEPROM WRITE FAILURE 
  TRIGGER-ON: here is an error in the ability to write information to be stored in the memory. 
  UNIT CONTROL: Alarm only 
  RESET CONDITION: Alarm may be manually reset via Keypad or by turning the unit off, then back on 
again. 
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the 
alarm(s). (See Note 1 Page 7-1) Operate the unit through the appropriate modes to see if any active alarm oc-
curs. Continue with the steps below as necessary. 
a. Check set point setting. 
Must be between -30°C to +32°C (-22°F to +89.6°F) 
Must be between -30°C to +32°C (-22°F to +89.6°F) 
a. Turn main switch off for 
30 seconds, then turn on. 
Microprocessor powers up OK. 
b. Alarm 246 remains active. 
Replace microprocessor. Refer to Section 5.4