62-61753-21   
Checking High Pressure Switch  
 
Do  not  use  a  nitrogen  cylinder  without  a 
pressure  regulator.  Cylinder  pressure 
I approximately  159.9  bar  (2350  PSIG). 
Do not  use oxygen  in  or  near  a  refrigerant 
system  as  an  explosion  may  occur.  
(See Figure 8-19) 
 
  1.  Cylinder Valve and 
Gauge 
  2.  Pressure Regulator 
  3.  Nitrogen Cylinder 
  4.  Pressure Gauge  
[0 to 27.2 bar  
(0 to 400 PSIG)] 
  5.  Bleed-Off Valve 
  6.  Switch 
Figure 8-20. Typical Setup for  
Testing High Pressure Switch  
a. Remove switch as outlined in preceding section 
b. Connect ohmmeter  or continuity light across  switch 
terminals.  Ohmmeter  will  indicate  resistance  and 
continuity light will be illuminated if switch closed af-
ter relieving pressure.  
c. Connect  switch  to  a  cylinder  of  dry  nitrogen.  (See 
Figure 8-19)  
d. Set  nitrogen  pressure  regulator  higher  than  close 
setting  for  switch  being  tested.  Pressure  switch 
open  and  closing  settings  are  provided  in  Section 
2.10.  
e. Close valve on cylinder and open bleed-off valve.  
f.  Open  cylinder  valve.  Slowly  close  bleed-off  valve 
and increase pressure until the switch opens. If light 
is used, light will go out and if an ohmmeter is used, 
the  meter  will  indicate  open.  Close  cylinder  valve. 
Slowly  open  bleed-off  valve  (to  decrease  pressure) 
until switch closes (light will illuminate or ohmmeter 
will indicate open).  
8.6.12  Pressure Transducers 
The  Compressor  Discharge  Pressure  Transducer 
(CDP)  has  a  range  of  0  to  34.0  bar  (0  to  500  PSIG) 
while  the  Compressor  Suction  Pressure  Transducer 
(CSP)  and  Evaporator  Pressure  Transducer  (EVOP) 
have a  range  of  -1  to  6.8  bar  (-14.7  to100  PSIG).  To 
test the transducers, do the following: 
NOTE 
The  Compressor  Discharge  Pressure  on  the 
microprocessor  Data  List  will  never  read  less 
than 0 bar/psig, even if it is exposed to a vac-
uum (such as when evacuating the system.) 
a. Verify that the wiring to the transducer is correct. 
b. Power up microprocessor, refer to Note 2, page 7-2. 
Check  Voltage  to  transducer  connector.  Voltage 
reading  between  A  (positive)  and  B  (negative) 
should be 5.0 VDC. 
c. To check the signal wiring, check continuity between 
the transducer connector C terminal and the follow-
ing microprocessor connector: 
CDP = 1MP-5, CSP = 1MP-29, EVOP = 1MP-17 
d. If  voltage  and  signal  wire  are  good,  replace  the 
transducer. The transducer may be removed by dis-
connecting  the  connector  and  quickly  backing  it  off 
the Schrader connection. 
8.6.13  Defrost Air Switch 
NOTE 
If the DTT temperature  is  above  4.4°C (40°F) 
defrost  cannot  be  initiated  and  the  Message-
Center will show "CANNOT START DEFROST 
CYCLE". 
a. To check the Defrost Air Switch, run unit in cooling 
and jumper across the air switch terminals. This will 
start  the  defrost  cycle  as  it  simulates  the  action  of 
the  defrost  air  switch.  Bypassing  the  switch  in  this 
manner operates all components involved in defrost. 
b. Unit  should  remain  in  defrost  until  DTT  reaches 
12.8°C  (55°F).  At  this  point  the  defrost  cycle  will 
terminate, and the unit will resume automatic opera-
tion. 
c. If  the  above  test  indicates  satisfactory  operation, 
test  DAS  settings  using  a  Magnehelic  gauge  
(P/N 07-00177) or similar instrument as follows.