62-11039 4-14
+1.8_F(+1.0_C)
+0.9_F(+0.5_C)
Setpoint
FALLING
TEMPERAT URE
RISING
TEMPERAT URE
-- 0 . 9 _F(--0.5_C)
-- 1 . 8 _F(--1.0_C)
High Speed
6 Cylinder Cool
Low Speed
6 Cylinder Cool
High Speed
6 Cylinder Heat
+2.7_F(+1.5_C)
-- 2 . 7 _F(--1.5_C)
+3.6_F(+2.0_C)
-- 3 . 6 _F(--2.0_C)
High Speed
6 Cylinder Cool
High Speed
6 Cylinder Heat
Low Speed
6 Cylinder Heat
UNIT OFF
STOP
UNIT OFF
STOP
CSMV CONTROLCSMV -- 0%
CSMV
-- 100%
CSMV -- 0%CSMV -- 100%
SMV
CONTROL
Figure 4 --4.Start --Stop -- Temperature Control Operating Sequence -- Perishable Range
+1.8_F(+1.0_C)
+0.9_F(+0.5_C)
Setpoint
FALLING
TEMPERAT URE
RISING
TEMPERAT URE
-- 0 . 9 _F(--0.5_C)
-- 1 . 8 _F(--1.0_C)
High Speed
6 Cylinder Cool
+2.7_F(+1.5_C)
-- 2 . 7 _F(--1.5_C)
+3.6_F(+2.0_C)
-- 3 . 6 _F(--2.0_C)
High Speed
6 Cylinder Cool
UNIT OFF
STOP
UNIT OFF
STOP
CSMV -- 0%
SMV
CONTROL
CSMV -- 0%
CSMV CONTROL
Figure 4 --5.Start --Stop -- Temperature Control Operating Sequence -- Frozen Range