62-11039 5-4
CONFIGURATION
SELECTIONS DESCRIPTION
HIGH SUCT PRESS SHUTDOWN
YES / NO YES = When alarm 27 is active the alarm light will
be on and the unit will shut off.
NO = When alarm 27 is active the alarm light will
be on and the unit will continue to run.
REFRIGERATION SYS
SHUTDOWN
YES /NO YES = When alarm 28 is active the alarm light will
be on and the unit will shut off.
NO = When alarm 28 is active the alarm light will
be on and the unit will continue to run.
COMPRESSOR ALARM
SHUTDOWN
(Special option card required)
YES / NO YES = The unit will shutdown and not restart when
alarms 13, 17, 18 or 56 occur 3 times within 2
hours.
NO = Normal shutdown rules for above alarms.
SUCTION PRESSURE
30 PSIG (2.0 BAR)
0--50psig(0to
3.4 Bar)
[in1psig(0.1Bar)
increments]
Pressure to maintain if discharge pressure trans-
ducer is opened or shorted.
CURRENT FOR S/S SHUTOFF
7.0A
1A TO 10A
(in 0.5A incre-
ments)
This is the maximum charging amps permitted for
start--stop off cycle.
VOLTAGE FOR S/S RESTART
12.2V
11.5 TO 12.8V
The engine will restart from a Start/Stop Off cycle
or a Sleep Mode Off cycle when the battery drops
to this value.
ALTERNATOR CHECK
SHUTDOWN:
YES / NO YES = When alarm 51 is active the alarm light will
be on and the unit will shut off.
NO = When alarm 51 is active the alarm light will
be on and the unit will continue to run.
ENGINE OIL LEVEL SWITCH YES / NO YES = An Engine Oil Level Switch is installed.
NO = An Engine Oil Level Switch is not installed.
ENGINE OIL LEVEL SHUTDOWN YES / NO YES = The low engine oil level alarm will shutdown
the unit.
NO = The low engine oil level alarm will not shut-
down the unit.
LOW COOLANT LEVEL YES / NO YES = A Coolant Level Sensor is installed.
NO = A Coolant Level Sensor is not installed..
FUEL TANK
NO DEVICE
SWITCH
INSTALLED
0 TO 100% SEN-
SOR
NO DEVICE = There is no Low Fuel Level Sensor
installed in the fuel tank.
SWITCH INSTALLED = A Low Fuel Level Switch is
installed in the fuel tank.
0 to 100% SENSOR = A Low Fuel Level Sensor is
installed in the fuel tank. The fuel level may be
read in the unit data list.