1-3 62-11039
WARNING
Relieve internal pressure of replacement
compressor by slightly loosening the bolts
of both service valve flanges/blank valve
pads and then lightly tapping the center of
the valve flanges/pads with a soft mallet to
break the seal.
WARNING
Do not use a nitrogen cylinder without a
pressure regulator. Cylinder pressure is
approximately 159.9 Bars (2350 PSIG). Do
not use oxygen in or near a refrigerant sys-
tem as an explosion may occur. (See
Figure 8 --32)
WARNING
The Compressor Discharge Pressure
T ransducer does not have a Schrader valve
in the connecting fitting. Any discharge
pressure remaining in the compressor will
be released when removing the CDP.
WARNING
Carrier Transicold does not recommend al-
lowing the compressor to pull less than 0
Bar/PSIG at any time.
CAUTION
Service Mode MUST be used whenever re-
moving refrigerant charge, refrigerant leak
checking or evacuating.
CAUTION
The display and MessageCenter may be-
have differently during the software loading
process, depending on the version of soft-
ware currently in the controller. DO NOT IN-
TERRUPT THE SOFTWARE INSTALLATION
PROCESS ONCE IT HAS STARTED.
CAUTION
It is important that communications be-
tween the Micro and the computer are not
disturbed during the software loading pro -
cess. If using a laptop computer, turn all en-
ergy saving features off. T urn off any screen
saver, or any hard drive time out settings.
CAUTION
Be certain that the clock you are using is ac-
curate. Also, some customers are located
in different time zones from the repair loca-
tion. If you know the repair location time
zone, enter that time. If you don’t, enter
your current time.
CAUTION
Use only Carrier Transicold approved Poly-
ol Ester Oil (POE). Buy quantities of one
quart or less. When using this hygroscopic
oil, immediately reseal. Do not leave con-
tainer of oil open or contamination will oc -
cur .
CAUTION
Unit uses R404A and POE oil. The use of in-
ert gas brazing procedures is mandatory for
all Carrier Transicold refrigeration units;
otherwise compressor failure will occur.
For more information Refer to Technical
Procedure 98-50553-00 Inert Gas Brazing