2 ZP3 Fire Panel User Guide
Basic system features
The ZP3 system incorporates a wide range of features and capabilities, including
these:
The ZP3 incorporates the proven ZP system of automatic contamination
adjustment for each sensor. This recalibrates each sensor as it becomes
contaminated, and provides a constant sensitivity even when sensors are
dirty.
Each sensor is individually adjustable for sensitivity, including different
sensitivities for day and night operation.
Selectable alarm verification allows the time integration of each sensor to be
set. Analogue sensors provide prealarm, alarm, service, and diagnostic
alarms.
The panel continuously checks every sensor for contamination, with
automatic alarm.
The system supports both fire and non-fire monitoring functions, e.g. door
open, fault alarms, etc.
The ZP-loop provides for addressable loop-powered sounders, reducing
wiring.
Each panel supports up to 50 zones, optionally 128. Built-in zone LEDs
display up to 50 zones, and extender panels provide LED display for up to
128 zones.
Each panel has the capacity for 896 programmable inputs and outputs, which
can be located with the panel, or remotely via serial connection.
Flash memory retains all programming and data, even if the panel is powered
down.