EasyManua.ls Logo

Carrier Ziton ZP3 - Fault Alarm Procedures; Types of Faults; Operator Actions for Fault Alarms

Carrier Ziton ZP3
45 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24 ZP3 Fire Panel User Guide
For example, remove smoke from the detectors or replace the glass in a call
point. When you press Reset, the system restores to its normal state.
Fault alarms
A fault alarm displays on the panel as described in Table 9 below. The actions
carried out upon receipt of a fault alarm depend upon the procedures at the site
where the system is installed. The following are generic guidelines only.
Table 9: Fault alarms annunciation and alarm
Description
Remarks
Common Fault
LED Illuminated.
Text display
Zone screen showing details of the
zone or category with the fault, and
a general description of the fault.
Panel
buzzer Sounding continuously.
Building
sounders Not sounding. Fault alarms are treated as a general alarm.
Auxiliary
functions Active, if configured to operate (e.g. advising a
remote manned centre,
calling maintenance staff, etc.).
Status
indicators Illuminated to indicate the affected system element. In addition, the
LEDs indicate which functions have been activated, such as advising
the remote manned centre, etc.
Delayed
functions Delayed LED illuminated for those functions that are programmed to
operate in response to the fault alarm, and are configured for delayed
operation. These could be remote centre alarms or control functions.
Types of fault
The panel continuously monitors both itself and all external wiring and devices for
abnormal conditions. Faults can be categorized as shown in Table 10 below.
Table 10: Fault alarms types of fault
Category
Description
Serious
faults A system fault that takes the entire system out of operation, such as a
processor failure. This requires immediate action.
Limited f
aults A fault that takes a small part of the system out of operation. This needs to
be repaired within the same day. Examples of limited faults are; a damaged
cable, or a mains failure where the batteries operate the system for the rest
of the day.
Operator action
1. Press the Accept button to acknowledge the alarm.
This silences the panel buzzer, and causes the flashing alarm indicators to go
steady.
Do not press the Reset or Silence Alarms buttons.
2. Call maintenance personnel to fix the fault.