20 ZP3 Fire Panel User Guide
Alarms by device
Press View Points to see current
alarms by device. The device screen
displays the exact address of the
device, and a message with its exact
location.
View Points
button
Zone screen
The following paragraphs describe how to read the LCD display when it indicates
an alarm. The Zone Screen shown in Figure 11 below indicates automatically
when an alarm is received.
Figure 11: Typical zone screen
HELP
ACCEPT
MUTE
BUZZER
RESET FIRE FAULT DISABLED OTHER
SILENCE
ALARMS
SOUND
ALARMS
MORE
VIEW
POINTS
Line 1
Line 2
Line 3
Line 4
Line 1: Alarm information
The left side of the line indicates the type of alarm that exists, for example
FIRE, FAULT, DISABLED, or OTHER”.
The word Zones indicates that you are viewing the zone screen.
The right side of the line shows the total number of current zone alarms
(events), for example 02.
Line 2: Details of first alarm
The event number is shown on the left side of the line.
The remainder of the line gives the description of the zone.
The time of the alarm, for example 06:37, is shown at the end of the line
(optional).
Note: In the default zone display, line 2 shows the first alarm received, as
indicated by the event number 01. When manually scrolling, the alarm shown in
line 2 changes to the next or previous event.
Line 3: Details of other alarms
The event number is shown on the left side of this line.
The remainder of the line gives the description of the zone, for example the
location.