ZP3 Fire Panel User Guide 27
Remarks
functions Delayed LED illuminated for those functions that are programmed to
operate in response to the alarm, and are configured for delayed
operation. These could be remote centre alarms or control functions.
Types of alarm
Other alarms can be categorized as shown in Table 15 below).
Table 15: Other alarms — types of alarm
Description
s Prealarms and alert alarms from smoke sensors and high-sensitivity
detectors.
Alarms from security interface devices.
-fire alarms Alarms from interface devices used for monitoring non-fire functions.
Services, maintenance, and preservice indications.
Operator action
1. Press the Accept button to acknowledge the alarm.
This silences the panel buzzer, and causes the flashing alarm indicators to go
steady.
Do not press the Reset button.
2. Take action appropriate for the type of alarm.
The type of alarm determines the action to take. For example, a “Prealarm”
could indicate a small quantity of smoke, and might require prompt attention.
3. Record the action taken in the logbook.
4. After resolving the alarm, press the Reset button.