EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
29 EN1Z-0970GE51 R0918
Example 2: Multiple EAGLE Controllers and Connected BACnet Modules
1 11 12 22 2
24V~
24V~
24V~
24V~
24~0
24~0
24~0
24~0
24 2425 2526 26
BACnet
Module #2
RS485 +
RS485 -
GND
BACnet
Module #4
RS485 +
RS485 -
GND
F1 F1F1 F1
230 V 230 V230 V 230 V
24 V 24 V24 V 24 V
L
GND-1 GND-1
+5V
ISO
+5V
ISO
RS485-1 (+) RS485-1 (+)RS485-1 (-) RS485-1 (-)
47 kOHM 47 kOHM
24 2425 2526 26
GND-1 GND-1
GND-1 GND-1
+5V
ISO
+5V
ISO
RS485-1 (+) RS485-1 (+)RS485-1 (-) RS485-1 (-)
550 OHM 550 OHM150 OHM 150 OHM550 OHM 550 OHM
BACnet
Module #1
BACnet
Module #3
BACnet
Module #N-1
BACnet
Module #N
GND-1
47 kOHM
GND-1
47 kOHM
EAGLE EAGLE EAGLE EAGLE
*CONNECT GND, IF AVAILABLE.
RS485-1 RS485-1RS485-1 RS485-1
END
END
BIAS
MID
MID
END
BIAS
MID
MID
END
BIAS
MID
END
END
BIAS
MID
Fig. 43. Connection of RS485-1 to a BACnet MS/TP Bus
Example 3: Multiple EAGLE Controllers and Connected BACnet Modules (with inserted termination resistor)
1 11 12 22 2
24V~
24V~
24V~
24V~
24~0
24~0
24~0
24~0
24 2425 2526 26
RS485 +
RS485 -
GND
BACnet
Module
RS485 +
RS485 -
GND
F1 F1F1 F1
230 V 230 V230 V 230 V
24 V 24 V24 V 24 V
L
GND-1 GND-1
+5V
ISO
+5V
ISO
RS485-1 (+) RS485-1 (+)RS485-1 (-) RS485-1 (-)
47 kOHM 47 kOHM
24 2425 2526 26
GND-1
GND-1 GND-1
+5V
ISO
+5V
ISO
RS485-1 (+) RS485-1 (+)RS485-1 (-) RS485-1 (-)
550 OHM 550 OHM150 OHM 550 OHM
GND-1
550 OHM
GND-1
47 kOHM
GND-1
47 kOHM
BACnet
Module #1
BACnet
Module #N
R
T
BACnet
Module #2
BACnet
Module #3
BACnet
Module #N-1
*CONNECT GND, IF AVAILABLE.
EAGLE EAGLE EAGLE EAGLE
RS485-1 RS485-1 RS485-1 RS485-1
120 Ohm
END
END
BIAS
MID
MID
END
BIAS
MID
MID
END
BIAS
MID
BIAS
END
BIAS
MID
Fig. 44. Connection of RS485-1 to a BACnet MS/TP Bus
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module (in this example, that is
the rightmost EAGLE, the 3-position slide switch of which has been set to "BIAS.")