EasyManua.ls Logo

CentraLine EAGLE - Connecting RS485-2 to the Modbus

CentraLine EAGLE
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-0970GE51 R0918 32
Connecting RS485-2 to the Modbus
With regards to Fig. 48, please note the following:
NOTE: Always power each EAGLE and the connected Modbus slaves via separate transformers.
NOTE: For "L," see section "RS485 Standard" on pg. 9.
NOTE: If any of the devices are electrically isolated, it is recommended that those devices be connected to signal ground.
See section "RS485 Standard" on pg. 9.
NOTE: Between devices equipped with non-isolated RS485 bus interfaces, potential differences of max. ±7 V are allowed.
Further, this bus should not extend beyond a single building.
Example: EAGLE Modbus Master Controller and Connected Modbus RTU Slaves (with inserted termination
resistor)
1 2
24V~
24~0
2930 31
GND-2
GND-2+5V
RS485-2 (+) RS485-2 (-)
550 OHM 550 OHM130 OHM
F1
230 V
24 V
R
T
RS485 +
RS485 -
GND
RS485 +
RS485 +
RS485 +
RS485 +
RS485 -
RS485 -
RS485 -
RS485 -
GND
GND
GND
GND
L
EAGLE
*CONNECT GND, IF AVAILABLE.
RS485-2
Modbus
Module
Modbus
Slave #1
Modbus
Slave #2
Modbus
Slave #3
Modbus
Slave #N-1
Modbus
Slave #N
120 Ohm
END
BI
A
S
MID
NO EFFECT ON RS485-2
Fig. 48. Connection of EAGLE Modbus Master Controller to Modbus RTU slaves via RS485-2
The termination resistor must be inserted directly into the terminals of the last Modbus RTU slave.

Table of Contents

Related product manuals