EasyManua.ls Logo

CentraLine EAGLE - Modbus Connection; Modbus Considerations; Connecting RS485-1 to the Modbus

CentraLine EAGLE
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
31 EN1Z-0970GE51 R0918
MODBUS CONNECTION
The EAGLE controller supports Modbus RTU Master functionality.
Modbus slaves can be connected to either of the two onboard RS485 interfaces (but not to both simultaneously): RS485-1
(consisting of push-in terminals 24 [GND-1], 25, and 26) or RS485-2 (consisting of push-in terminals 29, 30, 31 [GND-2]).
NOTE: GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)
Modbus Considerations
RS485-1 (isolated)
˗ Max. Modbus length: 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485 Standard" on
pg 9).
˗ Use only shielded, twisted-pair cable and daisy-chain topology.
˗ Must conform to EIA-RS485 cabling guidelines.
RS485-2 (non-isolated)
˗ Max. Modbus length: 1200 meters (9.6 – 76.8 kbps) or 1000 meters (115.2 kbps) (see also section "RS485 Standard" on
pg 9).
˗ Use only shielded, twisted-pair cable and daisy-chain topology.
˗ Ground noise should not exceed the EIA-485 common mode voltage limit.
˗ Must conform to EIA-RS485 cabling guidelines.
˗ Should not extend beyond a single building.
Max. no of Modbus devices per EAGLE: 32 (including the EAGLE, itself, which is counted twice)
Connecting RS485-1 to the Modbus
With regards to Fig. 47, please note the following:
NOTE: Always power each EAGLE and the connected Modbus slaves via separate transformers.
NOTE: For "L," see section "RS485 Standard" on pg. 9.
NOTE: If any of the devices are electrically isolated, it is recommended that those devices be connected to signal ground.
See section "RS485 Standard" on pg. 9.
Example: EAGLE Modbus Master Controller and Connected Modbus RTU Slaves (with inserted termination
resistor)
1 2
24V~
24~0
242526
F1
230 V
24 V
L
GND-1
GND-1
+5V
ISO
RS485-1 (+) RS485-1 (-)
550 OHM 150 OHM 550 OHM
RS485 +
RS485 -
GND
RS485 +
RS485 +
RS485 +
RS485 -
RS485 -
GND
GND
GND
R
T
RS485 -
RS485 +
RS485 -
GND
EAGLE
*CONNECT GND, IF AVAILABLE.
Modbus
Slave #1
Modbus
Slave #2
Modbus
Slave #3
Modbus
Slave #N-1
Modbus
Slave #N
120 Ohm
RS485-1
Modbus
Module
END
END
BIAS
MID
Fig. 47. Connection of EAGLE Modbus Master Controller to Modbus RTU slaves via RS485-1
The termination resistor must be inserted directly into the terminals of the last Modbus RTU slave.

Table of Contents

Related product manuals