If the conduit runs from the back of the SCE to the side(s), with rigid wireway elbows:
l
The rear conduit clearance from the front anchor bolt at grade is 620 mm (24.4 in) (a)
l
The recommended extra rear service clearance of open space (not necessarily at grade) is 925 mm
(36.4 in) (b)
If the conduit runs from the back of the SCE straight back:
l
The rear conduit clearance at grade is 470 mm (18.5 in) (a)
l
The recommended extra rear service clearance of open space (not necessarily at grade) is 775 mm
(30.5 in) (b) from the front anchor
If the site does not meet these basic requirements, contact ChargePoint before continuing.
For more information, access ChargePoint documents at chargepoint.com/guides.
Wheel Stops and Bollards
Bollards and wheel stops are not explicitly required by ChargePoint. However, ChargePoint recommends
these best practices and considerations when designing the site:
13