Line Color Definitions
OPTIONAL SHUNT TRIP CONDUCTORS
CELLULAR MODEM INSIDE PROVIDES NETWORK CLOUD CONNECTIVITY
DEFINITIONS
l
CPE : CHARGEPOINT CPE280 DISPENSER
l
DCS : DISCONNECT SWITCH WHERE REQUIRED PER NEC 110.58
l
DP-EV : DEDICATED EVSE ELECTRICAL PANELBOARD
l
GND. : GROUND (GROUNDING CONDUCTOR)
l
MAX. : MAXIMUM (MAXIMUM SIZE ALLOWED)
l
MIN. : MINIMUM (MINIMUM SIZE ALLOWED)
l
NEG. : NEGATIVE (NEGATIVE DC CONDUCTOR)
l
POS. : POSITIVE (POSITIVE DC CONDUCTOR)
l
STP : SHIELDED TWISTED PAIR
Each Express 280 requires a service panel breaker as follows:
Nominal Voltage Max AC Current Circuit Breaker Size
480 VAC (NA) 100 A 125 A (125% continuous load required for North America)
26
Wiring Diagram