NVF5 Series User Manual        Appendix A RS485-MODBUS 
Communication Instructions 
Appendix A RS485-MODBUS Communication 
Instructions 
A.1 Networking Mode 
NVF5 inverter provides RS485 communication interface and adopts the international 
standard Modbus communication protocol for Master-Slave communication. Users can 
achieve centralized control (set the control command and running frequency of inverter, 
modification of the related parameters, monitoring of inverter status and fault information 
etc.) through PC/PLC, host computer monitoring software etc., to adapt to the specific 
application requirements. 
As shown in figure A-1-1,the networking modes of NVF5 (as the slave station) include 
single master/ multiple slaves mode and single master/ single slave mode.   
Inverter
Host
(PLC)
Host
(PC)
Host
(PLC)
Adapter
RS232/RS485
RS232
Adapter
RS232/RS485
RS232
Inverter Inverter Inverter Inverter Inverter Inverter
Host
(PC)
RS485
RS485
RS485
...
 
Figure A-1-1 Networking Mode Diagram 
A.2 Interface Mode 
RS485 interface: Asynchronous, half-duplex. Default: 1-8-N-2  (Bit 1-start bit; bit 
8-data bit, no check, bit 2-stop bit, 9600bps, RTU, slave address: 0x01. For parameter 
setting, see description of Parameter List Group Fb . 
A.3 Communication Mode 
1.Inverter communication protocol is Modbus protocol, and supports RTU and ASCII 
protocols.   
2.The inverter is the slave and adopts master-slave point-to-point communication. 
When the master send commands using the Broadcast mode, the slave will not respond. 
3 . In the case of multi-machine communication or long-distance, connecting 
Termination resistors of (100 to 120) ohm on the positive and negative terminals of the 
signal line of master station communication  which  can improve the communication 
immunity. 
4.The inverter only provides one RS485 interface. If the communication port for 
peripheral equipment is RS232, RS232/RS485 conversion equipment should be added. 
- 101 -