NVF5 Series User Manual    Chapter 3 Installation and Wiring 
R is actual brake resistor resistance,P
  is brake resistor power. 
3.2.3  Output AC Reactor Descriptions 
The cable between Inverter and Motor should not be too long.If the cable is too long,the 
distributed capacitance will be large, the harmonic current will be generated easily. 
The output AC reactor should be selected when the motor cable is too long.Please refer 
to the table below: 
 
Catalog No. 
Current 
Min.Cable Length
(m) 
  AC output reactor 
 
NVF5-0.4/TS4-B  1.5  50 
NVF5-0.75/TS4-B  2.7  50 
NVF5-1.5/TS4-B  4.2  50 
NVF5-2.2/TS4-B  5.8  50 
NVF5-3.7/TS4-B  10.5  50 
NVF5-5.5/TS4-B  13  70 
NVF5-7.5/TS4-B  17  100 
3.3 Installation 
The inverter shall be installed at an indoor place ,good in ventilation and generally in a 
vertical mode. When using inverter, please pay attention to installation distance 
requirement.
 The following are examples of multiple side-by-side installations and multiple 
vertical installations.   
(1)multiple side-by-side installations 
 
Figure 3-3-1 Side-by-side Installatio Diagram 
- 16 -