NVF5 Series User Manual  Chapter 6 Parameter Function Description 
Chapter 6 Parameter Function Description 
6.1 Start Source Setting 
Command control is used to control inverter start、stop、run forward、run reverse、
jog. 
There are 4 types of command control:Integral Keypad、Terminal、Comm.、Remote 
Keypad,Command reference channel can be selected by parameter F0.01. 
F0.01 
Speed  Reference 
Channel Selection 
0 
0 
1 
Terminal 
2 
Comm. 
3 
6.1.1 Integral Keypad Command 
Setting parameter F0.01=0,Press RUN、STOP key to run or stop inverter.Press RUN 
key,RUN indicator light;In Run mode,Press STOP key to stop inverter,RUN indicator 
light off. 
6.1.2 Terminal Command   
Setting parameter F0.01=1,Start and Stop inverter by DI terminals.Setting parameter 
F5.08  select DI terminals control mode.There are four types of DI terminals control 
mode,Two Wire Control Mode1、Two Wire Control Mode 2、Three Wire Control Mode 1、
Three Wire Control Mode 2。 
Code  Name  Default 
Description 
F5.08 
Terminal 
Control Mode 
0 
0 
1 
2 
Three Wire Control 
Mode 1 
3 
Three Wire Control 
Mode 2 
Users can select DI1  ~  DI4 and HDI as DI terminals command channel by setting 
parameters F5.01  ~  F5.05 to select DI1  ~  DI4 and HDI function. 
 Two Wire Control Mode1:
As shown in the following figure,When K1 is closed,the inverter will run forward;
When K2 is closed,the inverter will run reverse;When K1、K2 is closed or opened at the 
- 38 -