NVF5 Series User Manual     Chapter 6 Parameter Function Description 
F4.13 
Digital Given 
0.0% 
(0.0 ~ 100.0)
% 
100%    motor 
rated voltage 
F4.14 
VF Separation Voltage 
Rising Time 
0.5s  (0.0 ~ 10.0)s  - 
F4.15 
VF Separation Voltage 
Dropping Time 
0.5s  (0.0 ~ 10.0)s  - 
F4.16 
VF Separation Max. 
Output Voltage 
100.0% 
F4.17~100.0% 
- 
F4.17 
VF Separation Min. 
Output Voltage 
0.0%  0.0%  ~  F4.16  - 
The acceleration time of V/F separation voltage refers to the time required for the 
output voltage to accelerate from 0 to the rated voltage of the motor,  the deceleration 
time of V/F separation voltage refers to the time required for the out voltage to decelerate 
from motor rated voltage to 0 . 
Output Vol. V
Time t
VF separation 
Max. output Vol.
V setting
VF separation Vol
. 
increase time
VF separation 
Min. output Vol.
VF separation Vol
. 
decrease time
 
Figure 6-5-4 V/F Separation Curve Setting 
6.6 Vector Control Parameters 
Vector control regulator is divided into speed control regulator and torque control 
regulator:Speed control mode is that the whole control takes the stable speed as the core 
to ensure that the running speed is consistent with the speed reference, and the maximum 
load capacity is limited by the torque limit;torque control mode is the whole control to 
stabilize the torque as the core to ensure that the actual output torque and torque  
reference consistent, and the output frequency is limited by speed limit.   
6.6.1 Vector Control Parameter Setting 
F3.00 
0 
0  ~  1 
0 : Speed 
- 67 -