NVF5 Series User Manual     Chapter 6 Parameter Function Description 
Output Vol.
Time
Output
Freq.
Time
Over voltage 
stall point
 
Figure 6-8-1 OverVoltage Stall Action Diagram 
 
Code  Name  Default  Setting Range  Description 
FE.04 
Overvoltage  Stall 
Protection 
Selection 
0 
0  ~  2 
0:Ineffective 
1:Effective   
2 :
FE.05 
0 
0  ~  100  0:Prohibit 
FE.06 
Overvoltage Stall 
Protection Voltage 
130% 
(120  ~  150)% 
- 
6.9 Protective Function 
6.9.1  Power On Start Protection 
 
Code  Name  Default 
Description 
F8.31 
Selection 
1 
0  ~  1 
0:No Applicable 
1:Start Protection 
By setting parameter F8.31(Start Protection)=1 to execute the inverter start protection:
If the running command is valid when the inverter is powered on (for example, the running 
terminal is closed before the inverter is powered on), the inverter does not respond, it must 
first cancel the running command, the running command is valid again, the inverter then 
responds.   
- 72 -