NVF5 Series User Manual     Chapter 6 Parameter Function Description 
(0.0~1000.0)V 
(0  ~  10)V 
(0  ~  10)V 
(0.01  ~  100.00)kHz 
(0  ~  1000)A 
(0  ~  1000)V 
Output Torque(+/-) 
-2  times Motor Rated Current~   +
2 
6.12 Ride Through Function 
The Ride Through function enables the system to run continuously during short time 
power failure. 
When a power failure occurs, inverter keeps in the Regenerative status, the DC Bus 
Voltage is maintained in FE.16,avoid inverter stop due to short time input voltage cut off   
to cause Undervoltage Fault. 
   
Figure 6-12-1 Ride Through Function 
FE.13 
Instantaneous power 
Off Action Selection 
0 
0  ~  2 
0:Ineffective 
1:Decel. 
2:Decel. Stop 
FE.14 
Judgement Voltage of 
Instantaneous Action 
90.0% 
(80.0  ~  100.0)
% 
Standard DC 
FE.15 
Instantaneous Power 
0.50s 
(0.00  ~  100.00)
s 
- 
- 85 -