NVF5 Series User Manual     Chapter 6 Parameter Function Description 
Output Vol. V
Output freq. f
Max. 
Output Vol.
Normal 
running freq.
V3
V2
V1
f1 f2 f3
0
(f1,V1)
multi-point VF 
curve point 1
(f2,V2)
multi-point VF 
curve point 2
(f3,V3)
multi-point VF 
curve point 3
 
Figure 6-5-2 Custom Multi-Point V/F Curve 
● Reduced Torque V/F Curve:Under the rated frequency, the relationship between the 
output voltage and the output frequency varies according to the 2nd power, 1.7th power 
and 1.2th power curves,this V/F curve is suitable for the load of fans and pumps. 
Output Vol. 
V
Output freq. f
Max.
Output Vol.
Normal 
Running Freq.
Linear 
Type
1.2th power V/F curve
1.7th power V/F curve
2.0th power V/F curve
Square 
Type
 
Figure 6-5-3 Reduced Torque V/F Curve 
6.5.2 V/F Seperation Curve Setting 
Code  Name  Default  Setting Range  Description 
F4.12 
Voltage Channel 
0  0  ~  3 
0 :
Setting 
1:AI1 
2:
AI2 
3:
Reserve 
Note:100% 
Corresponding 