Power on
   Need motor  
auto tuning
Confirm the main 
circuit and control 
circuit correct
Select motor 
control mode by 
parameter F0.00
Set parameter F2.22 
to 1, press RUN key 
to conduct static 
motor auto tuning
Can disconnect 
motor load?
Input the correct motor 
nameplate data
Set parameter F2.22 
to 2, press RUN key 
to conduct rotate 
motor auto tuning
Set reference frequency by 
parameter F0.05
When the inverter is ready, press Run key to start 
the motor without load, measure and check the 3-
phase current balance
After testing completed, stop the inverter, prepare 
to set other parameters as equipment required
Input the correct motor nameplate 
data in parameter group F2 
(F2.01~F2.06)
Set NVF5 motor control mode according 
to parameter F0.00 definition. The default 
mode is V/F control.
After power on, the default 5.00Hz 
will be displayed on NVF5 integral 
keypad screen normally
Set Accel. and Decel. time
Set Accel.time and 
Decel.time by parameter 
F0.14 and F0.15
Default reference frequency is 
5.00Hz. It can be changed as 
required.
Yes
No
Refer to Chapter 3 -“Installation 
and Wiring” for check correct 
wiring
If the inverter is running normally without load, the 
inverter can be tested with load, measure and 
confirm the 3-phase current balance, and also 
confirm the current less than rated motor current
The output current value of 
inverter is almost the same as 
the value displayed on 
integral keypad of NVF5,
motor running direction refer 
to parameter F0.06
After testing completed, stop the inverter 
and set other parameters as required 
Record the current value and parameters
Run the motor at 5.00Hz and 
check the motor running direction
If the motor runs reverse, 
change parameter F0.06 or 
change the 3-phase motor 
cables.
Yes
No