NVF5 Series User Manual       Chapter 7 Troubleshooting 
E.OL2 
Inverter 
Overload 
1、  Incorrect Motor Nameplate 
Motor auto tuning 
2、Excessive load 
Enlarge inverter power rate 
3、Excessive DC Brake 
current, increase brake 
4、  Accel. Time too short 
Increase accel. time 
5、  Low grid voltage 
Check grid voltage 
6、  Unsuitable V / F curve 
Adjust V/F cruve or adjust 
manual torque boost 
E.OL3 
Supply 
1、DC Bus Voltage    fluctuates 
around undervoltage threshold 
Asking for Chint technical 
support 
E.EF  External Fault 
External Fault Emergency Stop 
Terminal Effective 
connecting with external 
E.EEP 
Read-Write 
Control Parameter Read-Write 
Error 
Asking for Chint technical 
support 
E.CE 
Serial Interface 
error 
1、  Host computer problem 
Check host computer 
wiring 
2、Comm. Cable problem 
Check Comm. wiring 
3、Comm. Parameters problem 
Set correct comm. 
parameters 
E.ItE 
Current 
detection 
circuit 
abnomaly 
1、
 
Loose control board wiring 
or plug 
Check and rewire 
2、  Aux. power supply damage 
Asking for Chint technical 
support 
3、  Hall Element Damage 
4、  Amplification circuit 
E.tE 
Auto Tuning 
Problem 
1、Set Wrong Motor Data 
Set correct motor data 
2、  Reverse Auto Tuning is 
prohibited in reverse running   
Disable Reverse 
3、  Poor contact of motor 
Check motor cable 
4、Auto Tuning Overtime 
(Frequency Max.) 
whether is samller than 
E.StG 
Motor short circuit to ground  Check motor cable 
- 94 -