21798-01-EN Rev. 04 Page 25
4.8.3 Advanced Receiver Connections
Receiver connections: ANA1, ANA2, ANA3, DIGITIAL1, DIGITAL2, and 485
have been designed to operate while maintaining safety rated conditions.
ANA1 Hi/LO is a current input.
ANA2 HI/LO is a differential voltage input (a resistor is needed external to
the box to sense current).
ANA3 HI/LO can either be one differential voltage input or 2 digital I/Os
(individually configurable as digital inputs or digital outputs).
DIGITAL1 and DIGITAL2 are digital I/Os (individually configurable as
digital inputs or digital outputs).
Note: Digital I/Os default to inputs. When configured as outputs, they are
switches to ground thru a 100-ohm resistor (so the states are either open or
“ground”).
For Analog Current Inputs: the max rated current is +100mA
For Analog Voltage inputs: the max rated differential voltage (HI to LO) is
+12.5V
For the Digital Inputs:
Logic ‘0’ is or any voltage between 0V and 2V (switch closure to GND).
Logic ‘1’ is and open input or any voltage between 3V and 30V.
For the Digital Outputs:
Logic ‘0’ is 100 Ohms to GND with the max allowed current sink is 25mA
Logic ‘1’ is an open circuit with the max voltage range of 0V to 30V.
4.8.3.1 Install Hydraulic Pressure Sensor (Optional Equipment)
Refer to Figure 19 Advanced Receiver Wiring Diagram:
The Hydraulic Pressure Sensor is an advanced feature option that requires Receiver
Module CiDRA P/N:21718-0003 and Receiver Cable CiDRA P/N:21828-02.
For Hydraulic Pressure (HP) installation procedure see listed steps below.
Make sure Drum is not rotating, and hydraulic pressure (HP) is de-
energized (Existing analog HP Gauge is reading 0 PSI).
Disconnect existing female fitting from either the Pump end or Gauge end
of the Hydraulic line. (Figure 20 shows the HP installed at the Pump end.)
Connect CiDRA supplied fitting (or equivalent) in between the
disconnected section of hydraulic hose.
Securely tighten all fittings.