7.5.5.3.- Conguration of the RS-485 gateway parameters
Table 149:Modbus memory map: Modbus TCP (Bridge) communications module (Table 3)
Conguration of the Modbus TCP parameters
Configuration variable Address Valid data margin Default value
Baud rate F500
0: 1200 - 1: 2400 - 2: 4800 -
3: 9600 - 4: 19200 - 5: 38400 -
6: 57600 - 7: 76800 - 8: 115200
4
Parity F501
0 : No parity
1: Odd parity
2: Even parity
0
Length F502 1: 8-bit 1
Stop Bits F503
0: 1 stop bit
1: 2 stop bits
0
Note: The 4 registers must be written at once (as a group), otherwise it will respond with an
error.
7�5�5�4�- MAC address of the Modbus TCP module
The function implemented for this variable is:
Function 0x04: reading registers.
Table 150:Modbus memory map: Modbus TCP (Bridge) communications module (Table 4)
MAC address of the Modbus TCP module
Configuration variable Address Valid data margin
MAC address F236 - F238 3 integers : 6 characters