4. Insert the stripped end of the ground lead all the way into the ground lead receptacle on the –48 VDC
input power supply, and tighten the receptacle screw using a 3.5 mm flat-blade screwdriver to a torque
of 0.5 to 0.6 Nm.
5. Insert the stripped end of the positive lead all the way into the positive lead receptacle and tighten the
receptacle screw using the same 3.5mm flat-blade screwdriver.
6. Repeat this step for the negative lead.
7. After tightening the receptacle screw for the ground, positive, and negative –48 VDC-input leads, use
a cable tie to secure the three leads to the power supply faceplate, as shown in Figure 24: Cisco ASR
1002-X Router –48 VDC Power Supply Terminal Block Cable Connections, on page 35. When securing
the ground, positive, and negative –48 VDC-input leads to the power supply faceplate, leave a small
service loop in the ground lead to ensure that the ground lead is the last lead to disconnect from the
power supply if a great deal of strain is placed on all three leads, as shown in Figure 24: Cisco ASR
1002-X Router –48 VDC Power Supply Terminal Block Cable Connections, on page 35.
8. Connect the ground, positive, and negative leads to the power source.
9. Turn the branch source breaker on.
10. Place the –48 VDC Standby switch in the On (|) position. The power supply LEDs light when power
is supplied to the router.
DETAILED STEPS
Step 1 At the rear of the router, check that the power supply Standby switch is in the Standby (see Figure 24: Cisco ASR
1002-X Router –48 VDC Power Supply Terminal Block Cable Connections, on page 35 ) position.
Figure 24: Cisco ASR 1002-X Router 48 VDC Power Supply Terminal Block Cable Connections
Negative lead3Ground lead with service loop and tie wrap1
–48 VDC power supply Standby switch4Positive lead2
Step 2 Ensure that the negative and positive leads are disconnected from the site power source.
Cisco ASR 1002-X Router Overview and Installation
35
Cisco ASR 1002-X Router Overview and Installation
Connecting the 48 VDC Input Power to the Cisco ASR 1002-X Router

Other manuals for Cisco ASR 1002-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco ASR 1002-X and is the answer not in the manual?

Cisco ASR 1002-X Specifications

General IconGeneral
Form FactorRack-mountable
Rack Units2RU
Integrated ServicesYes
Maximum Memory16 GB
Built-in Gigabit Ethernet Ports6
Input Voltage100-240 VAC
Operating Temperature32 to 104°F (0 to 40°C)
RedundancyPower supply redundancy
Network Interface ModulesUp to 4 SPA/SIP slots
Embedded Services Processor (ESP)ESP-20
Maximum Packet per Second (PPS)15 Mpps
Height3.5 inches
Fixed Ports6 GE ports
Memory4 GB (default), 16 GB (maximum)
Power SupplyDual power supplies (AC or DC)
Dimensions (H x W x D)3.5 x 17.5 x 19.0 in (8.9 x 44.5 x 48.3 cm)