2.4.2 Wiring of emergency stop input (TB3)
Rated voltage 24V ±10%, rated current within 5mA
The emergency stop input will be effective as default setting.
Refer to the “AX Series TS, TH Type manual” for setting instructions.
Emergency stop is a “b” contact input. Thus it will take effect when emergency stop input
(TB3) becomes open. (Emergency stop using PROFIBUS will be effective when the input
data is OFF
Emergency stop can be inputted by TB3’s input terminal or CN3’s PROFIBUS
communications and if one of the inputs becomes open (or off), it will be recognized as
emergency stop.
Input to TB3 is necessary to release the emergency stop.
The cable sheath peeling length should be 8 or 9mm.
The applicable cable is AWG20 to 24 (single cable) or AWG20 to 22 (stranded cable).
TB3:emergency
stop input (I/O)
CN3:emergency stop
Input (serial)
Emergency
stop
Input processing
Serial communication
processing
ABSODEX
Emergency stops if either
input becomes open (or off).
External power supply 24VDC
(Prepared by customer)
*
The polarity of the external power supply
can be inverse.
8~9mm
AWG20~22