SM-A20758-A/3 1. PRODUCT OVERVIEW
20 2020-10-06
Process data OUT
Start energization to this product after clearing Process Data OUT to "0 ".
Unintended pressure may occur.
The setting in this product can be changed with IO-Link communication from the master to
the device (this product) and key operation.
The setting that be set at last is reflected as this product’s setting because there is no hierarchical
relationship and precedence on both sides. In case that the setting is set on the device side, it is
synchronized with the master side. But sometimes it is not reflected to the display unless the
display is update or the setting uploaded depending on master. Take care of that.
The value in Process Data OUT can be operated only on the master side.
The value cannot be reflected as Process Data OUT even if the setting is changed with key
operation on the device. Confirm Process Data IN and Parameter when confirming the product
setting state on the master side.
Note 1: Refer to "エラー! 参照元が見つかりません。 Preset input"
Note 2: When turning off the power of the EVD, be sure to set the Process data OUT pressure to zero (Bit16-31 = 0) ,
next to stop (Bit0 = False) and then turn off the power. The excessive operation data of solenoid valve are saved
when transitioning from start (Bit0 = True) to stop (Bit0 = False).
Note 3: In case that controlling is performed using IO-Link communication, set this bit to 1(True). If this bit is 0(False), controlling
cannot be performed.
Observation
Solenoid valve energizing time
Operating Time
0 h to 9,999,999 h
【0 to 9,999,999】
Excessive operation time of supply
solenoid valve
Number of excessive operations of supply
solenoid valve
0 times to 9,999,999
times
Excessive operation time of
exhaust solenoid valve
Number of excessive operations of exhaust
solenoid valve
0 times to 9,999,999
times
R: read
Note 1: Be able to count more than 10 years of energization time.
Calculation: 9,999,999h÷7,488h≈1335.5 Year
24h/Day×26Day/Month×12 months=7,488h/Year
Note: The excessive operation data of solenoid valve are saved when transitioning from start (Bit0 = True) to stop (Bit0 = False).
Please save the data periodically on the master side in case of unpredictable situations such as a power supply failure.
When turning off the power of the EVD, be sure to set the Process data OUT pressure to zero (Bit16-31 = 0),
next to stop (Bit0 = False) and then turn off the power.