SM-A20758-A/3 1. PRODUCT OVERVIEW
20 2020-10-06
Process data OUT
CAUTION
Start energization to this product after clearing Process Data OUT to "0 ".
Unintended pressure may occur.
The setting in this product can be changed with IO-Link communication from the master to
the device (this product) and key operation.
The setting that be set at last is reflected as this product’s setting because there is no hierarchical
relationship and precedence on both sides. In case that the setting is set on the device side, it is
synchronized with the master side. But sometimes it is not reflected to the display unless the
display is update or the setting uploaded depending on master. Take care of that.
The value in Process Data OUT can be operated only on the master side.
The value cannot be reflected as Process Data OUT even if the setting is changed with key
operation on the device. Confirm Process Data IN and Parameter when confirming the product
setting state on the master side.
Note 1 Refer to "エラー! 参照元が見つかりません。 Preset input"
Note 2 When turning off the power of the EVD, be sure to set the Process data OUT pressure to zero (Bit16-31 = 0) ,
next to stop (Bit0 = False) and then turn off the power. The excessive operation data of solenoid valve are saved
when transitioning from start (Bit0 = True) to stop (Bit0 = False).
Note 3: In case that controlling is performed using IO-Link communication, set this bit to 1(True). If this bit is 0(False), controlling
cannot be performed.
Observation
Index
Sub
index
Item
Value
Access
Data
length
Format
0x0400
0
Solenoid valve energizing time
Operating Time
Note 1
0 h to 9,999,999 h
0 to 9,999,999
R
4byte
Integer32
0x0401
0
Excessive operation time of supply
solenoid valve
Note 1
0 h to 9,999,999 h
R
4byte
Integer32
0x0402
0
Number of excessive operations of supply
solenoid valve
0 times to 9,999,999
times
R
4byte
Integer32
0x0403
0
Excessive operation time of
exhaust solenoid valve
Note 1
0 h to 9,999,999 h
R
4byte
Integer32
0x0404
0
Number of excessive operations of exhaust
solenoid valve
0 times to 9,999,999
times
R
4byte
Integer32
R read
Note 1: Be able to count more than 10 years of energization time.
Calculation 9,999,999h÷7,488h1335.5 Year
24h/Day×26Day/Month×12 months=7,488h/Year
Note: The excessive operation data of solenoid valve are saved when transitioning from start (Bit0 = True) to stop (Bit0 = False).
Please save the data periodically on the master side in case of unpredictable situations such as a power supply failure.
When turning off the power of the EVD, be sure to set the Process data OUT pressure to zero (Bit16-31 = 0),
next to stop (Bit0 = False) and then turn off the power.
PD
PD0
PD1
Bit
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
MSB
LSB
Data Name
Set Value for pressure
Data Range
2byte
Format
UInteger16
PD
PD2
PD3
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Data Name
Unused
Preset Note 1
-
-
-
-
-
-
-
Start/Stop
Note 2,3
3
2
1
Data Range
0 to 7
-
-
-
-
-
-
-
True/False
Format
UInteger3
-
-
-
-
-
-
Boolean