Control procedure using IO-Link communication
Normal Mode
The pressure can be controlled with the "Set Value for pressure" of the Process Data OUT.
The set value cannot be changed by key operation.
◼ Setting method using IO-Link communication
[Parameter setting]
• Input signal setting
"0: Normal Mode" is written to Index:0x010F (Input
setting).
[Operation]
Process Data OUT
• Setting active state (pressure controlled state)
Set the "Start/Stop" bit of the Process Data OUT to "1" to create an active state.
Pressure can be controlled by setting the "Set value for pressure" of the Process Data OUT.
Set pressure range for each model and unit
• A pressure setting shall be entered in 4 digits. When you do not use IODD, you do not need to
enter a decimal point; when you use IODD, you must include a decimal point.
• Do not enter a value outside the allowable range. User's programs should control the Process
Data OUT setting so that it is within the allowable range.