SM-A20758-A/3 3. USAGE
41 2020-10-06
◼ How to operation (IO-Link communication)
<Parameter settings>
Switch output 1 setting
• Switch output 1 OFF setting
Index: Write "0: OFF" to 0x0101.
• Switch output 1 mode 1 setting
Index: Write "1: Mode 1" to 0x0101.
Index: Write lower limit value of Mode 1 to 0x0103.
Index: Write higher limit value of Mode 1 to 0x0104.
• Switch output 1 mode 2 setting note 2
Index: Write "2: Mode 2" to 0x0101.
Index: Write lower limit value of Mode 2 to 0x0105.
Index: Write higher limit value of Mode 2 to 0x0106.
Switch output 2 setting
• Switch output 2 OFF setting
Index: Write "0: OFF" to 0x0102.
• Switch output 2 mode 1 setting
Index: Write "2: Mode 1" to 0x0102.
Index: Write lower limit value of Mode 1 to 0x0107.
Index: Write higher limit value of Mode 1 to 0x0108.
• Switch output 2 mode 2 setting note 2
Index: Write "2: Mode 2" to 0x0102.
Index: Write lower limit value of Mode 2 to 0x0109.
Index: Write higher limit value of Mode 2 to 0x010A.
Note 1: The set value represents a percentage of the full scale (FS).
(Ex.) To set a pressure of 100 kPa for 500 kPa type, set 20 by calculating as follows: 100/500 x 100 = 20.
Note 2: When Mode 2 is used, it should be set so as to achieve (Lower limit value + 10) ≤ Upper limit value.
When this requirement is not met, the Switch output is always OFF. 0x8D12 or 0x8D13 is generated in the Event Code of Diagnosis.
12 or 13 is displayed as the error code (Bit4-7) of PD5. See 1.5.7 Diagnosis, and 5.2 Error Code.
[Confirmation]
Process Data IN
Check the Switch output of the Process Data IN.
Switch output 1 is stored in Bit 8, and Switch output 2 is stored in Bit 9.
For the Output, "0: OFF" and "1: ON".