EasyManua.ls Logo

CKD SHD3025 - Operation Stop; Energy Saving Unit

Default Icon
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
<SM-13024-A>
8
Pressuredewpoint(℃)
(NOTE)
-20 -30 -40 -60
(reference)
Atmosphericdewpoint
(℃) -40 -48 -57 -74
Time(h) 6 12 24 72
NOTE:Pressuredewpointis0.7MPa.
14) Sinceithassetupbeforehand,donottouchtheneedlevalve(referto6-3clause)attachedtothe
dewpointsensorlowerpart.
5-2Operationstop
1)
Closetheinletandoutletvalves.
2)
PresstheSTOPbutton.DEWPOINTisstilldisplayedevenatthistime.
3)
TurnOFFthemainpowersupply.
4) Sincedryerpassesairalsoduringastop,besuretocloseinletandoutletvalve.
5-3Energysavingunit
Thisproductisequippedwithanenergysavingunitasastandardaccessory. Thefollowing
showstheoutlineoftheenergysavingunit.
1)
TurnONor OFFtheenergysaving unitusingthe ECOMODE button. Whentheenergy
savingunitispoweredON,theindicationlampislit.Additionally,thelampislittoshowthe
dewpointvalue,whichissetatthistime.
2)
To change the set dew point, keepthe ECO MODE button pressed for 2 sec. with the
energysavingunitturnedOFF([ECO]lampisoff.).SinceECOMODEblinksinthatcase
anditdisplaysthatachangeispossible,pleasebesuretocheckblinking.Whenpressing
theSTOPbuttoninthisstate,thenumericvaluecanbechanged.Whenadesirednumeric
valueisshown,presstheECOMODEbuttontosetthisvalue.(Blinkingchangestolighting.)
3)
ThedewpointsetfortheG-type(standardtype)isdifferentfromthatsetfortheM-type
(high-gradetype).
Pressuredewpoint
-10℃ -20℃ -40℃ -60℃
G-type
○ ○ ○
-type
○ ○ ○
4)
Thedewpoint,atwhichtheoperationisactuallychangedtotheenergysavingoperation,is
set at a level slightly lower than the set dew point level. Therefore, the energy saving
operationisnotstartedatthesetdewpoint.
-10℃setting -20℃setting -40℃setting -60℃setting
Dewpointchangedto
energysaving
Lessthan-14℃ Lessthan-24 Lessthan-44 Lessthan-64℃
Dewpointwhich
energysavinggoesout
Over-12℃ Over-22℃ Over-42℃ Over-62℃
5) Ifthe flowconsumptionissmall,the dewpoint does notbecomeworse with theenergy
saving operation started. At this time, the operation is forcibly returned to the normal
operationafter1hourhaselapsed.

Related product manuals