EasyManua.ls Logo

Cleaver-Brooks CBH 40 - Page 40

Default Icon
75 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter
4-Starting
and
Operating
Instructions
above
the
operating
limit
temperature
control
set-
ting.
Inspect
the
high-low
flame
control
for
proper
set-
ting
which
should
be
slightly
lower
than
that
of
the
operating
limit
control.
Adjustment
procedures
for
these
controls
is
covered
in
Chapter
5.
Inspect
the
low
water
cut-off. Check for
freedom
of
float
and
verify
that
control
is
functioning
properly.
In
the
event
the
boiler
is
equipped
with
optional
control
devices
not
listed
here,
ascertain
that
their
settings
are
correct.
If
additional
information
is
required
see
your
local
Cleaver-Brooks
representa-
tive
or
contact
Cleaver-Brooks.
Set
damper
positioning
switch
at
"low".
Leave
burner
switch
"off'
but
close
all
other
power
en-
trance
switches
(supplied
by
others).
C.
Oil
BURNER START -UP
(100 and 200 Series)
PREPARATION
FOR
INITIAL
FIRING
Verify
that
the
driving
belt
for
the
oil
pump
is in
place.
Temporarily
close
the
oil
shut-off
valve
(Figure
1-1).
On a 200 series
boiler,
set
the
gas/oil
selector
switch
to
"Oil".
Close
main
gas
cock
and
open
pilot
gas
cock.
Open
all
valves
in
the
oil
suction
line
and
oil
return
line.
The
line
from
the
storage
tank
to
the
pump
should
be filled
with
fuel.
Short
suction
lines
may
be filled by use
of
the
fuel
pump.
Long
suction
lines
and
those
of
large
diamet-er
pipe
should
be
filled
by
priming
or
other
means.
Manually
hold
in
the
blower
motor
starter
until
the
oil
pump
picks
up
and
circulates
oil.
The
oil
flow
may
be
verified
when
the
pressure
gauge
in-
dicates
a
steady
pressure
reading
of
175 psi (ap-
proximately).
If
no
pressure
·shows
on
the
gauge
af-
ter
a few
moments
stop
the
pump
and
prime
the
suction
line.
Continue
this
procedure
until
the
oil
flow is
established.
A
vacuum
(or
compound
pressure
-vacuum)
gauge
installed
in
the
oil
suction
line
will
reveal
the
tightness
of
the
system.
Its
readings
should
be
ob-
served
and
recorded
for
future
guidance.
Refer
to
Chapter
5 for
further
information
on
the
oil
piping
system.
Check
that
damper
positioning
switch is
set
at
"low".
Turn
burner
switch
to
"on".
The
blower
motor
will
start
and
oil
pressure
will
be
indicated
on
the
gauge.
The
timer
in
the
programming
con-
trol
will begin
rotating.
The
damper
will
open
for
the
pre-purge
period
and
allow
a flow
of
air
through
the
fireside
area
of
the
4-2
pressure
vessel.
The
damper
motor
will
return
to
the
low fire
position
after
this
pre-purge
is com-
pleted.
The
low fire switch
must
be closed for ac-
tion
to
continue.
Now check for
ignition
spark.
When
the
"pilot
ignition"
legend
appears
on
the
timer
dial,
the
ignition
transformer
is energized. An
electric
spark
should
be
visible
when
viewed
through
the
rear
door
sight
glass.
If
the
unit
has
a
gas
pilot,
its
flame
can
be
seen.
The
main
burner
will
not
light
since
the
oil
shut-
off
valve
is closed.
With
evidence
of
a good
spark
(or
gas
pilot)
and
proper
oil
pressure,
the
unit
is
ready
to
be
fired.
Turn
burner
switch
to
"off'.
The
programmer
will
complete
its
cycle
and
stop.
Reset
the
safety
switch
in
the
event
programmer
locked
out
prior
to
the
burner
switch
being
turned
off.
Review
the
sequence
of
operation
given in
Chapter
3 for a
complete
description
of
the
action
that
takes
place
during
a
starting
and
operating
cycle.
INITIAL
START-UP
AND
FIRING
Set
damper
position
switch
to
"low".
Open
the
manual
fuel oil
valve
(Figure
1-1).
Turn
burner
switch
"on".
After
the
pre-purge
period
the
burner
will
light
and
operate
at
its
low fire
rate.
In
some
instances
on
initial
firing,
air
may
be
trap-
ped
in
the
fuel
lines
preventing
ignition
until
it
is
completely
expelled
and
replaced
by
fuel oil.
It
may
be
possible
for
the
burner
to
go
through
several
cycles
until
all
lines
are
filled
with
oil.
If
ignition
does
not
then
occur, do
not
repeat
un-
successful
lighting
attempts
without
re-checking
burner
and
pilot
adjustments.
On
an
ignition
failure
the
blower
will
continue
running
to
purge
the
boiler
of
any
unburned
fuel
vapors
before stopping. After
ignition
failure
wait
a few
moments
before
re-setting
safety
switch.
CAUTION:
The
burner
and
control
system is de-
signed
to
provide
a
pre-purge
period
of
fan
operation
prior
to
establishing
ignition
spark
and
pilot
flame.
Do
not
attempt
to
alter
the
system
in
any
way
that
might
circumvent
this
feature.
When
flame
is
established
leave
the
burner
in
low
fire
position
for
approximately
30
minutes
or
until
boiler
is
properly
warmed,
unless
it
reaches
its
nor-
mal
operating
pressure
or
temperature
sooner.
A
hot
water
boiler
must
have
a
continuous
flow
of
system
water
through
the
vessel
during
the
warm-
up
period.
If
conditions
permit,
the
entire
water
content
of
the
system
and
boiler
must
be
warmed
prior
to
increasing
fuel
input.
As
normal
pressure
or
temperature
is
approached
at
low fire,
turn
the
damper
positioning
switch
to
"high".
Observe
the
burner
as
it
progresses
to
high

Table of Contents

Related product manuals