Hawk 1000 Section 4 — System Configuration
Part No. 750-366 4-9
If a valid user name and password are entered, the operator will be allowed to change data. The current user
login status can be seen in the top right corner of each screen.
The color of the pushbutton will also indicate if the user has proper access rights.
Pressing the button of the value that needs modifying will pop-up a numeric keypad, allowing the operator to
enter the new value. Notice that there is a range of valid entries at the top of the numeric keypad. An out-of-
range entry will show up in red and require re-entering an acceptable value.
Enter the desired value and press the Enter key. If the entry is valid, the value will be accepted and the keypad
will disappear. Note that all entries can be made by touching the HMI screen or by using the HMI keypad.
Boiler Media
Select Steam or Hot Water depending on the type of system.
Boiler Type
The Boiler Type will display the proper Boiler graphic on the Boiler overview screen
.
The three choices for
Boiler Type are: Firetube, Flextube and M4/M5
Boiler Type is also used to set limits on the maximum entry allowed for Safety Valve Setpoint (steam) or Max
Rated Temperature (hot water).
Maximum Rated Temperature (Hot Water)
All Types = Between 200-400 Deg F
Safety Valve Setpoint Max
Firetube 400 psi
Flextube 250 psi
M4/M5 600 psi
Numerical values
may be entered
from here or from
the popup numeric
pad on the screen
Popup keypad Invalid entry