Wired Sensor Type (Setup Step 30)
RETURN, OUTDOOR, SUPPLY = the sensor
temperature which is reported to Skyport to
monitor only.
REMOTE = the sensor can be used for
temperature control.
Control to Sensor (Setup Step 31)
Select LOCAL SENSOR ONLY to control
to the temperature sensor inside the
thermostat.
Select WIRED SENSOR ONLY to control to a
temperature sensor connected to the RS &
R terminals of the thermostat backplate.
Select AVERAGE LOCAL AND WIRED
SENSORS to control to the average of those
two temperatures.
NOTE: for wireless sensor control,
additional options appear on the Skyport
website.
Aux Use (Setup Step 32)
Select DEHUMIDIFIER or HUMIDIFIER
to specify what type of equipment is
connected to the D / H output.
User Setup
27
Occupied – If selected and the dry contact is active AND the time period
schedule is running, the thermostat is forced into OCCUPIED 1 settings
from the internal schedule. The ‘occupied 1’ icon will flash to indicate that
the schedule has been suspended and forced into occupied.