16
from the ductwork during maximum capacity
operation. Range will depend on model and
maximum cooling capacity selection.
Low Dehum Air ow Con gures the unit
air ow while operating at minimum capacity
in the dehumidi cation mode. Range will
depend on model and minimum cooling
capacity selection.
High Dehum Air ow Con gures the unit
air ow while operating at maximum capacity
in the dehumidi cation mode. Range will
depend on model and maximum cooling
capacity selection.
Constant Fan Air ow Con gures the unit
air ow while operating in the continuous fan
mode. Range will depend on unit model.
Heat O Delay This setting determines
whether or not (and how long) the blower will
continue to operate after the compressor has
cycled o at the end of each heating cycle.
Valid range: 0 seconds to 255 seconds.
Cool O Delay This setting determines
whether or not (and how long) the blower will
continue to operate after the compressor has
cycled o at the end of each cooling cycle.
Valid range: 0 seconds to 255 seconds.
Unit Con guration
The Unit Con guration settings allow the
installing technician to con gure the thermostat
to the installed equipment. NOTE. Unit
Con g is only necessary when replacing an
EXM controller. The Unit Con g settings are
programmed at the factory when the unit is
built.
Heat Pump Family Select the family of heat
pump installed.