HW Pump Con g (If Applicable)
Water Heating Delta T Sets the potable
water ow rate for the water heating mode.
The variable speed potable water pump will
adjust the potable water ow to maintain the
selected temperature di erence between the
entering and leaving potable water during
the water heating mode. Valid range: 8.0°F to
12.0°F.
Thresholds
This section con gures the temperature, time,
and capacity thresholds associated with the
heating, cooling, and hot water (if applicable)
equipment. You must con gure the Equipment
settings before setting the thresholds. Only the
applicable threshold settings will be displayed.
Allow Auto Heat/Cool
Allows the user to be able to operate the unit in
the auto changeover heat/cool mode. Select Yes
for the user to be able to operate the thermostat
in the auto heat/cool mode, otherwise select No.
Heat/Cool Min Delta
Selects the minimum temperature di erence
between the heating and cooling set points
when the thermostat is operated in the auto
changeover heat/cool mode. Valid range: 2°F to
10°F. The default value is 5°F.
Advanced Settings
Allows the installer to select the controller to
con gure, typically an EXM.
To con gure thresholds
on the iGate
™
Connect
thermostat:
From the Home screen,
press MENU.
Select Settings ▶
Installation.
Select Thresholds.