20
temperature drops more than this amount,
the potable water heating mode will be
terminated and the space heating mode
will be activated. Valid range: 0.5°F to 1.5°F.
Default is 1.0°F.
Aux Heat DeadBand Con gures the
amount of space temperature droop
allowed from the heating setpoint at
maximum unit capacity before allowing
auxiliary heat for space heating. Valid
range: 0.0°F to 5.0°F. Default is 1.0°F.
Anticipator Con gures the sensitivity of
the thermostat to the space temperature.
A lower setting will cause the unit to
respond more rapidly to changes in
space temperature. A higher setting will
cause the unit to respond more slowly to
changes in space temperature. Valid range:
1 to 10. Default is 5.
Compressor ASCD Con gures the
minimum amount of time the compressor
will remain o between cycles. Valid
range: 5 minutes to 8 minutes. Default is 5
minutes.
AWS – WXM Settings (If Applicable)
HW Heat DeadBand Con gures the
amount of droop allowed from the potable
Hot Water setpoint before activating water
heating. Valid range: 10°F to 25°F. Default
is 15°F.
Temp Correction
Adjusts the current space temperature displayed
on the thermostat by the selected amount. Valid
range: –10°F to +10°F in 0.5°F increments.