EVH-X SPACE 2.1 - 12.1
M0SM10N17-03
General
The indicated operations should be done by
qualified technician with specific training on the
product.
The electrical and hydraulic connections upon
request; the remaining work on the system is the
responsibility of the installer.
Agree upon the start-up date with the service
centre sufficiently in advance.
For details refer to the different manual sections.
Before checking, please verify the following:
the unit should be installed properly and in
conformity with this manual
the electrical power supply line should be
sectioned at the beginning
the line sectioning device is open, locked and
equipped with the suitable warning signs
ensure no voltage is present
After turning off the power, wait at least 10
minutes before accessing to the electrical panel or
any other electrical component.
Before accessing check with a multimeter that
there are no residual stresses.
Preliminary checks
Unit OFF power supply
1 safety access
2 functional clearances
3 structure integrity
4 ventilatori girano liberamente
5 unit on vibration isolators
6 unit input water filter + shut-off valves for
cleaning
7 vibration isolators on water connections
8 expansion tank (indicative volume = 10% system
content)
9 minimum system water content
10 cleaned system
11 loaded system + possible glycol solution +
corrosion inhibitor
12 system under pressure
13 vented system
14 refrigerant circuit visual check
15 earthing connection
16 power supply features
17 electrical connections provided by the customer
Start-up sequence
Power unit ON
1 compressor crankcase heaters operating at least
since 8 hours
2 off-load voltage measure
3 phase sequence check
4 unit ON
5 load voltage measure and absorptions
6 measure return and supply water temperature
7 check no anomalous vibrations are present
8 climatic curve personalization
9 climatic curve personalization
10 scheduling personalization
11 complete and available unit documentation
Refrigerantion circuit
1 Visually check the refrigerating circuit: the
presence of oil stains can mean leakage
(caused, for example, by transport, handling or
other).
2 Check that the refrigerating circuit is under
pressure: use service pressure gauges to check
that the refrigerant circuit is pressurized.
3 Ensure that all the service outlets are closed
with the proper caps; if caps are not present a
leak of refrigerant is possible.
4 Aprire tutti i rubinetti del circuito frigorifero (se
presenti).
Water circuit
1 Before realizing the unit connection make sure
that the hydraulic system has been cleaned up
and the clearing water has been drained .
2 Check that the water circuit has been charged
and pressurised .
3 Check that the cut-off valves on the circuit are
in the "OPEN" position.
4 Check that no air is present in the circuit, if
required, evacuate using the air bleeding valve
placed at the system
5 When using antifreeze solutions, make sure the
glycol percentage is suitable for the type of use
envisaged.. table page following
Neglecting the washing will lead to several filter
cleaning interventions and at worst cases can
cause damages to the exchangers and the other
parts.
8 START-UP
Weight of glycol (%) 10 20 30
Freezing temperature (°C) -3,9 -8,9 -15,6
Safety temperature (°C) +1 -4 -10
Glycol solutions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET EVH-X SPACE 3.1 and is the answer not in the manual?

CLIVET EVH-X SPACE 3.1 Specifications

General IconGeneral
BrandCLIVET
ModelEVH-X SPACE 3.1
CategoryAir Conditioner
LanguageEnglish

Related product manuals