58
EVH-X SPACE 2.1 - 12.1
M0SM10N17-03
11 GENERAL TECHNICAL DATA
Water flow-rate
Size 2.1 3.1 5.1 7.1 10.1 12.1.
Q min [l/s] 0,16 0,23 0,28 0,35 0,56 0,71
Q standard (1) [l/s] 0,37 0,48 0,65 1 1,47 1,74
Q max [l/s] 0,46 0,74 0,94 1,39 2,04 2,28
Minimum and maximum admitted water flow from the unit
1- Water flow rate at nominal conditions with standard water flow and in/out water temperature 5°C.