control mode in parallel-to-mains operation is switched to BasePF (i.e. #SysPFCtrl 
PtM = BASEPF). 
 
The required power factor is adjusted by the setpoint 
#SysPwrFactor.  
The baseload is adjusted by the logical (functional) analog 
input MPF:AnExSysBPF.  
 
NOTE:  
If the external source is selected the logical analog input must be configured at 
each gen-set to the identical source. See the note at the setpoint 
SysBaseLdMode.  
 
This setpoint is used for adjusting the starting point of the Power derating 1 
function, where the gen-set nominal power is still 100% of the setpoint Nomin 
power. 
See the chapter Power derating for details. 
NOTE:  
The setpoint actual physical dimension depends on configuration of the physical 
analog input to which the logical input PowerDerating1 is assigned.  
 
This setpoint is used for adjusting the end point of the Power derating 1 function, 
where the gen-set nominal power is reduced to the value adjusted by setpoint 
Derated1 pwr. 
See the chapter Power derating for details. 
NOTE:  
The setpoint actual physical dimension depends on configuration of the physical 
analog input to which the logical input PowerDerating1 is assigned.