EasyManua.ls Logo

ComAp IG-NTC GC - Page 175

ComAp IG-NTC GC
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
175
Value: Reg16
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller which has address corresponding with
the bit position plays active role in the power management. Bit 0 represents
address 1 etc. This value contains information about controllers with addresses 1-
16.
Value: Reg32
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller which has address corresponding with
the bit position plays active role in the power management. Bit 0 represents
address 17 etc. This value contains information about controllers with addresses
17-32.
Value: GL16
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the bank controller which has address corresponding
with the bit position has BCB closed. Bit 0 represents address 1 etc. This value
contains information about controllers with addresses 1-16.
Value: GL32
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the bank controller which has address corresponding
with the bit position has BCB closed. Bit 0 represents address 1 etc. This value
contains information about controllers with addresses 17-32.
Value: Engine state
Group
Info
Units
-
Related FW
3.0

Table of Contents

Related product manuals