IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
196
Available in IS-NT only.
Binary input: PulseCounter 4
Related FW
3.0
Description
This is the input of the PulseCounter #4 module. The module counts pulses at the
input and if the input pulses counter reaches value given by the setpoint
ConvCoefPulse4, the counter value PulseCounter 4 (in the group Statistic) is
increased by 1 and input pulses conter is reset to 0. Both counter value and input
pulses counter are stored in the nonvolatile memory.
The PulseCounter modules are intended e.g. for connecting external energy or
fuel meters with pulse outputs.
NOTE:
Minimal pulse width as well as minimal pause between two succesive pulses is
100ms.
NOTE:
The counter value can be reset in the InteliMonitor statistics window.
NOTE:
Available in IS-NT only.
Binary input: Timer block 1
Related FW
3.0
Description
This input is used to disable temporarily the output from the Timer channel #1.
NOTE:
See also the setpoint TimerChannel 1 and output TimerAct 1-4.
NOTE:
See the chapter Timers for more details about timers.
Binary input: Timer block 2
Related FW
3.0
Description
This input is used to disable temporarily the output from the Timer channel #2.
NOTE:
See also the setpoint TimerChannel 2 and output TimerAct 1-4.
NOTE:
See the chapter Timers for more details about timers.
Binary input: Timer block 3
Related FW
3.0